Calculate voltage drop with stated units, an editable scenario and a worked result breakdown.

For a two-wire DC circuit with equal outgoing and return conductors, voltage drop is current multiplied by the loop resistance. Using one-way length L, conductor area A and resistivity ρ gives ΔV = 2LIρ/A. A 10 m run at 5 A through 2.5 mm² copper at 0.017241 Ω·mm²/m gives 0.68964 V.

Your numbers

BROWSER-LOCAL INPUTS

Your inputs stay in this browser. No account needed.

RESULT

Your result

Enter your values and select Calculate.

Check the units and assumptions before using this result.

METHOD

How the voltage drop calculator works

How to use this calculator

Enter measured values in the stated units and check which assumptions are fixed. Calculate, review the breakdown, then change one input for a consistent comparison.

What the result means

The conductor length in a complete current path includes both the supply and return. Calculator ForEver doubles the entered one-way length for this equal-conductor DC model. It calculates resistance, voltage drop and resistive loss from a fixed resistivity. This estimate does not size a protective device, determine allowable ampacity or model alternating-current impedance. A wire with an acceptable calculated drop can still be unsuitable for the current, installation or environment.

The formula

Loop R = 2 × length × copper resistivity / area; drop = current × loop R

A worked example

10 m one-way copper, 2.5 mm² and 10 A gives about 1.37928 V drop under the model.

Assumptions & methodology

DC two-wire copper at approximately 20°C, with equal outgoing and return conductors. No AC reactance, three-phase model, contact resistance, temperature correction, ampacity or code sizing. A drop exceeding supply indicates inconsistent assumed current for an ordinary passive load. Results are rounded for display; intermediate calculations retain precision. This tool is informational and does not replace institutional or professional guidance.

References

OpenStax: resistivity and resistance · OpenStax: electric power and energy

WORK THROUGH THE DETAILS

Using your voltage drop result

Follow the copper example through resistance and power

With 0.017241 Ω·mm²/m resistivity, 10 m one-way length and 2.5 mm² area, loop resistance is 2 × 10 × 0.017241 / 2.5 = 0.137928 Ω. At 5 A, voltage drop is 0.68964 V and cable heating is I²R = 25 × 0.137928 = 3.4482 W. On a 12 V source, the drop represents 5.747% of the supply. This arithmetic holds current fixed; it does not solve a load whose current changes when its terminal voltage changes.

Keep resistivity and temperature assumptions visible

The copper value used in the example is a reference resistivity near room temperature. Conductor resistance can rise with temperature, and alloy composition or construction can change it. The model does not compute a conductor operating temperature or adjust resistance from heating. Connections, switches and terminals can add resistance that is absent from the straight-wire expression. When comparing a field measurement with the estimate, account for those additional parts and the conditions under which the measurement was made.

Compare area and length without assuming compliance

If the example area rises from 2.5 to 5 mm², loop resistance and voltage drop halve. If the one-way run doubles from 10 to 20 m at unchanged area, both double. These proportional checks help identify a unit error. They do not replace ampacity, insulation, protective-device or installation requirements. Electrical rules can distinguish voltage-drop design guidance from conductor thermal limits. Use the applicable engineering and installation method for an actual circuit.

Interpret a large drop as a model or design question

A computed drop approaching or exceeding the source voltage needs scrutiny. The fixed-current assumption may be incompatible with the actual source and load, or the selected conductor may have excessive resistance. Subtracting the arithmetic drop does not demonstrate that a load will operate normally at the resulting terminal voltage. This tool excludes AC reactance, three-phase geometry, transient startup current, fault current and contact resistance, so it should not be treated as a complete circuit simulation.

INTERPRETATION

Understanding voltage drop results

Enter cross-sectional area rather than wire diameter

The area field uses square millimeters. A 2.5 mm diameter circle has area π × 1.25², approximately 4.9087 mm²; it is not a 2.5 mm² conductor. Wire gauge labels need a separate applicable area conversion. Use the metallic conductor area rather than the outside diameter of insulation. A mistaken area changes resistance inversely, so doubling the entered area halves the modeled drop for the same current and length.

Distinguish one-way length from loop length

For 10 m from source to load with another equal 10 m return, the model uses 20 m of conductor. Enter 10 m in the one-way field. Entering the complete 20 m loop there would cause the calculator to double it again and overstate resistance by a factor of two. Different supply and return conductors need separate resistance calculations before summing; this equal-area model cannot represent that arrangement through one average diameter.

RELATED GUIDES

Related questions and worked examples

Read a worked explanation before trying another calculation.

QUESTIONS

Voltage Drop questions

Does the calculator use three-phase voltage-drop equations?+

No. Its factor of two describes an equal outgoing and return pair in a DC circuit. Three-phase and AC impedance models need different inputs and equations.

Is the calculated power loss the load power?+

No. I²R describes heat dissipated in the modeled conductors. The load receives the remaining electrical power under the fixed-current and source-voltage assumptions.